NEMA Enclosure Types

2023-07-26 14:14:44 Young 80

NEMA MOTOR


Non-Hazardous Locations

Type 1 : General Purpose - Indoor

  • Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt.

Type 2 : Drip-Proof - Indoor

  • Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment, to provide a degree of protection against falling dirt, and to provide a degree of protection against dripping and light splashing of liquids.

Type 3 : Dusttight, Raintight, Sleettight - Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and that will be undamaged by the external formation of ice on the enclosure.

Type 3R : Raintight, Sleet Resistant - Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, and snow; and that will be undamaged by the external formation of ice on the enclosure.

Type 3S : Dusttight, Raintight, Sleettight - Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, and windblown dust; and in which the external mechanism(s) remain operable when ice laden.

Type 4 : Watertight, Dusttight, Sleet Resistant - Indoor & Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, and hose-directed water; and that will be undamaged by the external formation of ice on the enclosure.

Type 4X : Watertight, Dusttight, Corrosion-Resistant - Indoor & Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and corrosion; and that will be undamaged by the external formation of ice on the enclosure.

Type 5 : Dusttight, Drip-Proof - Indoor

  • Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against settling airborne dust, lint, fibers, and flyings; and to provide a degree of protection against dripping and light splashing of liquids.

Type 6 : Occasionally Submersible, Watertight, Sleet Resistant - Indoor & Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during occasional temporary submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure.

Type 6P : Watertight, Sleet Resistant Prolonged Submersion - Indoor & Outdoor

  • Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against hose-directed water and the entry of water during prolonged submersion at a limited depth; and that will be undamaged by the external formation of ice on the enclosure.

Type 12 : Dusttight and Driptight - Indoor

  • Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against dripping and light splashing of liquids.

Type 12K : Dusttight and Driptight, with Knockouts - Indoor

  • Enclosures constructed (with knockouts) for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against dripping and light splashing of liquids.

Type 13 : Oiltight and Dusttight - Indoor

  • Enclosures constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt; against circulating dust, lint, fibers, and flyings; and against the spraying, splashing, and seepage of water, oil, and noncorrosive coolants.

For enclosures used in

Hazardous Locations

Type 7 : Class I, Group A, B, C or D Hazardous Locations - Indoor

  • Enclosures constructed for indoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 70.

Type 8 : Class I, Group A, B, C or D Hazardous Location - Indoor & Outdoor

  • Enclosures constructed for either indoor or outdoor use in hazardous locations classified as Class I, Division 1, Groups A, B, C, and D as defined in NFPA 70.

Type 9 : Class II, Group E, F or G Hazardous Locations - Indoor

  • Enclosures constructed for indoor use in hazardous locations classified as Class II, Division 1, Groups E, F, or G as defined in NFPA70.

Type 10 : Requirements of Mine Safety and Health Administration

  • Enclosures constructed to meet the requirements of the Mine Safety and Health Administration, 30 CFR, Part 18.

For more detailed and complete information, NEMA Standards Publication 250-2003, Enclosures for Electrical Equipment (1000 Volts Maximum) should be consulted.


Phone Number
Inquiry Form
E-Mail
主站蜘蛛池模板: 免费视频在线视频观看1 | 国产人成精品午夜在线观看 | 视频一区中文字幕 | 91成人免费观看网站 | 日本免费一级 | 国产一区二区三区免费观看 | 免费观看一级特黄欧美大片 | 国产伦久视频免费观看 视频 | 在线观看91精品国产入口 | 澳门四虎影院 | 玖操网| 成人免费无毒在线观看网站 | 精品999久久久久久中文字幕 | 国内精品视频在线播放一区 | 国产三级在线看 | 国产日韩欧美亚洲综合首页 | 亚洲m男在线中文字幕 | 香蕉久草视频 | 亚洲国产精品线在线观看 | 日本高清加勒比 | 一级aaaaaa片毛片在线播放 | 看黄a大片 免费 | 亚洲成片观看四虎永久 | 一区二区三区高清在线观看 | 4hc44四虎www在线影院男同 | 性激烈的欧美暴力三级视频 | 国产精品欧美在线不卡 | 四虎欧美在线观看免费 | 精品国产理论在线观看不卡 | 国产精品视频一区二区三区不卡 | 六月天综合网 | 香蕉视频网站入口 | 视频一区 在线 | 美女91 | 国产码一区二区三区 | 精子网久久国产精品 | 亚洲欧美成人在线 | 久久综合九色综合97手机观看 | 久久精品视频9 | 国产精品三级视频 | 成人a视频|